Terms
The straight socket system consists of an integral bell and spigot where the bell is bonded on. The spigot end easily slides into the belled end. This joining system is intended for use with Champion Fiberglass epoxy adhesive.
Request Information
Unit of Measure
Items
Straight Socket Joint Tubular Size (ID) Straight Conduits

2 Inch (in) Nominal Size Extra Heavy Wall, Bullet Resistant ID Aboveground Straight Conduit with Straight Socket

Straight Socket Joint Tubular Size (ID) Straight Conduits

3 Inch (in) Nominal Size Extra Heavy Wall, Bullet Resistant ID Aboveground Straight Conduit with Straight Socket

Straight Socket Joint Tubular Size (ID) Straight Conduits

4 Inch (in) Nominal Size Extra Heavy Wall, Bullet Resistant ID Aboveground Straight Conduit with Straight Socket
Description N/A The straight socket system consists of an integral bell and spigot where the bell is bonded on. The spigot end easily slides into the belled end. This joining system is intended for use with Champion Fiberglass epoxy adhesive.
Brands N/A Champion Fiberglass®, Inc.
Type N/A ID Aboveground Straight Conduit with Straight Socket
Nominal Size N/A 2 in N/A 3 in N/A 4 in
Wall Thickness N/A
Length (L) N/A 10 ft
Color N/A Black
End Type N/A Bell End
Industry Standards/Certifications N/A Underwriters Laboratories (UL)
Application N/A Highest level of physical protection, Class 1 Div 2 & Class 1 Zone 2 Applications
General Information N/A Fiberglass Conduit Specifications for Use Below Ground

The conduit shall be fiberglass conduit, also known as Reinforced Thermosetting Resin Conduit (RTRC), manufactured using the single circuit filament winding process. Multi circuit windings are not allowed. The conduit shall have a winding angle as close as possible to 54.75 degrees.

The resin system shall be epoxy based, with no fillers, using an anhydride curing agent. The fiberglass shall consist of continuous E-glass roving. The conduit shall not contain any halogen compounds containing chlorine, bromine, fluorine and iodine in more than trace amounts when burning.

Conduit and elbows shall be manufactured from the same resin/hardener/glass systems manufactured by the same filament wound system.

Fiberglass conduit fittings and accessories shall be manufactured using one of two manufacturing procedures. The first method shall use the same process, methods, and components as used to manufacture the fiberglass conduit. The second method shall use the compression molding process, Sheet Molding Compound (SMC), for the manufacture of the finished component. The SMC material shall be a vinyl ester resin with +30% reinforcement of glass. The glass fibers should be approximately 1" in length. The SMC material shall be fire resistant to UL 2515.

Conduit shall be integral bell and spigot or bonded coupling and spigot.

Conduit, elbows and fittings are specified for use throughout a temperature range of -60ºF (-51ºC) to 250ºF (121ºC).

Manufacturer shall have a current Certificate of Compliance, issued by an independent and accredited company, with an ISO 9001:2008 Quality Management System.